Top Quality 60Hz 3 Phase Portable Power Quality Analyzer

Top Quality 60Hz 3 Phase Portable Power Quality Analyzer


Negotiable Min Order Quantity Unit

Required Quantity
Place of Origin
China
Payment Terms
T/T
Production method
Negotiable
Shipping / Lead Time
Negotiable / Negotiable
Keyword
electric power, electric motor, 3 phase handheld power quality analyzer
Category
Electrical Instrument

Guangzhou Xuan Tong Electric Technology Co. Ltd

Membership
BIZ
Country / Year Established
China China / 2014
Business type
Distributor
Verified Certificate

8

Product name Top Quality 60Hz 3 Phase Portable Power Quality Analyzer Certification -
Category Electrical Instrument Ingredients -
Keyword electric power , electric motor , 3 phase handheld power quality analyzer Unit Size -
Brand name - Unit Weigh -
origin China Stock -
Supply type - HS code -

Product Information

 

 

Specification

    P6300  handheld power qualityanalyzer, support to measure the power frequency system of 50Hz/60Hz powergrid, it can record all power quality parameters including of harmonic,voltage, current, frequency, fluctuation, flicker, power and 3-phase imbalance,etc. The 6300  possesses high class power quality measurement function,meanwhile it provides professional host computer analyze software to processsecondary analysis, and provides user the most accurate power fault diagnosisanalysis.

 

General Parameter
Parameter Parameter type Description
Environment working environment temperature 0℃~+45℃,humidity <90rh% 
memory environment temperature -20℃+50℃,humidity <95rh% (noncondensing) 
Memory type TF card
capacity 8G
Power supply adapter input 110V-240V,50Hz
adapter output 15V,3A
Battery type chargeable polymer li-ion battery,5000mAh 
battery working time ≥5h
battery charge time minimum 5h(environment temperature 25℃)
power saving function LCD backlight brightness adjustable, standby time adjustable
Display size 112.8×84.6mm
color 260k color
resolution 640×480
brightness max 350 cd/m²(Typ.),adjustable
contrast 500:1(Typ)
visual angle 70/70/50/70 (Typ.)(CR ≥ 10) (left/right/up/down)
Security meet standard GB 4793.1-2007/IEC 61010-1:2001, CATIII 1000V/CATIV 600V
banana input end CATIII 1000V/CATIV 600V
Crosstalk among voltage input end  under nominal frequency -60dB
voltage and current input end under nominal frequency -95dB
Common-mode rejection CMRR >60dB
Measure standard measure method IEC 61000-4-30
measure feature IEC 61000-4-30 class A
flicker  IEC 61000-4-15
harmonic IEC 61000-4-7
power decompoistion IEEE 1459
Electromagnetic compatibility standard class 4:GB/T 17626.2-2006 electrostatic discharge immunity
class 3:GB/T 17626.3-2006 RFEMS (radio-frequency electromagnetic field radiated immunity)
class 3:GB/T 17626.4-2008 Electrical fast transient burst immunity
class 3:GB/T 17626.5-2008 Surge (impact) immunity
class 3:GB/T 17626.8-2006 PFMF (Power Frequency Magnetic Field Immunity)
class 3:GB/T 17626.9-1998 Pulse Magnetic Field Immunity
class 3:GB/T 17626.12-1998 Oscillatory waves immunity
Environment reliability standard GB/T 2423.1-2008  low temperature
GB/T 2423.2-2008  high temperature
GB/T 2423.4-2008  Alternating hot and humid
GB/T 2423.5-1995  impact
GB/T 2423.10-2008 shake
GB/T 2423.22-2002 temperature variation
Measure parameter
Function Parameter type Description
Recorder oscilloscope A、B、C、N Each phase voltage and current waveform in real time
voltage current frequency frequency value, voltage effective value, voltage semi-wave effective value, voltage positive peak, voltage negative peak, voltage waveform factor, current effective value, current semi-wave effective value, current positive peak, current negative value, current waveform factor
power and electric energy active power, reactive power, apparent power, power factor, displacement power actor, active electric energy, reactive electric energy, apparent power electric energy
voltage harmonic  THD、DC、1-50times harmonic、0-49times inter-harmonics、1-35times ultraharmonics
current harmonic THD、DC、KF、1-50times harmonic、0-49times inter-harmonics、1-35times ultraharmonics
harmonic power THD、DC、1-50times harmonic power
flickering PST(short flicker)、PLT(long flicker)
imbalance positive sequence voltage and current, negative sequence voltage and current, zero sequence voltage and current,  unbalance degree
energy consumption active, reactive, apparent power decomposition, line loss power, line loss charge, pollution assess
demand demand
event record voltage swell and sag, voltage interruption, stroke current,short flicker out-of-limit, long flicker out-of-limit,voltage up out-of-limit, voltage down out-of-limit, frequency up out-of-limit, frequency down out-of-limit,,steady-state voltage fluctuation, voltage imbalance out-of-limit, voltage THD out-of-limit, voltage 1-50 times harmonic out-of-limit, current 2-50 times harmonic out-of-limit
Inverter DC DC voltage, DC current, DC power, ripple voltage, ripple voltage containing rate
AC frequency, voltage effective value, current effective value, total apparent power, total active power, total power factor, fundamental power, fundamental power factor
efficiency conversion efficiency
Transient voltage  voltage effective value, voltage semi-wave effective value, voltage positive peak, voltage negative peak 
current harmonic current effective value, current semi-wave effective value, current positive peak, current negative peak
frequency frequency
event record  voltage swell, voltage dip, voltage interruption
Monitor Monitor voltage effective value, 1-50times voltage harmonic, PLT, voltage dip, voltage swell, voltage interruption, steady-state voltage fluctuation, voltage imbalance degree
Parameter accuracy
Parameter Parameter type Description
Frequency nominal frequency 50Hz/60Hz
measure method operation by 10/12 circle
resolution 0.001Hz
measure width 42.5Hz - 69Hz
measure accuracy ±0.001Hz
Voltage effective value measure method operation by 10/12 circle square root value
resolution 0.001V
measure range 1V - 1000V
measure accuracy 0.1% of nominal voltage
Current effective value measure method operation by 10/12 circle square root value
resolution 0.001A
measure range different range by different transformer
measure accuracy 0.1%+CT accuracy
Power measure method active power: square of 10 circle wave voltage current  Instantaneous value
apparent power: 10 circle voltage effective value multiply current effective value 
reactive power: square of apparent power  minus  square root of active power
power factor: active power ratio apparent power
resolution 0.001W
measure range due to voltage measure range and current transformer measure range
measure accuracy 0.5%+CT accuracy
Voltage/Current harmonic measure method conform to IEC61000-4-7,  analyze window range 10 circle
measure type effective value, containing radio, phase angle
times/frequency 50times /50Hz-2500Hz
measure accuracy voltage harmonic >1% nominal value:deviation < 1% indication
voltage harmonic < 1% nominal value:deviation < 0.05% nominal voltage value
current harmonic >3% nominal value:deviation < 1% indication+CT accuracy
current harmonic < 3% nominal value:deviation < 0.05% current measure range+CT accuracy
Voltage/Current inter-harmonic measure method conform to IEC61000-4-7,  analyze window range 10 circle
measure type effective value, containing radio, phase angle
times/frequency 50times /25Hz-2475Hz
measure accuracy voltage harmonic >1% nominal value:deviation < 1% indication
voltage harmonic < 1% nominal value:deviation < 0.05% nominal voltage value
current harmonic >3% nominal value:deviation < 1% indication+CT accuracy
current harmonic < 3% nominal value:deviation < 0.05% current measure range+CT accuracy
Harmonic power measure method conform to IEC61000-4-7,  analyze window range 10 circle
measure type effective value, containing radio, phase angle
times/frequency 50times /50Hz-2500Hz
measure accuracy voltage current harmonic >1% nominal value:deviation < 1% indication+CT accuracy
voltage current harmonic < 1% nominal value:deviation < 0.05% nominal value +CT accuracy
Voltage/Current ultraharmonic measure method conform to IEC61000-4-7,  analyze window range 10 circle
measure type effective value, containing radio, phase angle
times/frequency 35times /2100Hz-8900Hz
measure accuracy voltage harmonic >1% nominal value:deviation < 1% indication
voltage harmonic < 1% nominal value:deviation < 0.05% nominal voltage value
current harmonic >3% nominal value:deviation < 1% indication+CT accuracy
current harmonic < 3% nominal value:deviation < 0.05% current measure range+CT accuracy
Imbalance degree measure method voltage negative sequence imbalance degree: negative sequence voltage ratio positive sequence voltage
voltage zero sequence imbalance degree: zero sequence voltage ratio positive sequence voltage
current negative sequence imbalance degree: negative sequence current ratio positive sequence current
current zero sequence imbalance degree: zero sequence current ratio positive sequence current
resolution 0.001%
measure accuracy voltage imbalance degree: ±0.2%
current imbalance degree: ±0.5%
Flicker measure item short flicker(PST), long flicker(PLT)
measure method according to  IEC61000-4-15 operate PST(10 mins)PLT(2 hours)
measure range 0 - 20
measure accuracy ±5%

 


 

B2B Trade

Price (FOB) Negotiable transportation -
MOQ Negotiable Leadtime Negotiable
Payment Options T/T Shipping time Negotiable

Guangzhou Xuan Tong Electric Technology Co. Ltd

Country / Year Established
China China / 2014
Membership
BIZ
Business type
Distributor

8

President
Grace Chang
Address
R512, Jinhaodingsheng Building, No.705 dashi Section, 105 National Road, Panyu District, Guangzhou, China
Product Category
Power Supplies
Year Established
2014
No. of Total Employees
51-100
Company introduction

 

Guangzhou Xuan Tong Electric Technology Co. Ltd was established by a group of vigorous, capable and professional electric persons in 2014.

Featured with resource integration of power products, Xuan Tong Electric bases on its professional electric experience to develop and provide electric energy testing & monitoring instruments and meters for industrial users at home and abroad. Series products include Power Quality Analyzer, Integrated Protection Devices for Low Voltage Motors, Relay Protection Testing Device, Generator and Reactive Compensation Capacitance Detection Device. Xuan Tong Electric devotes to solve potential electric security problem and safeguard production for industrial users.

Xuan Tong Electric possesses a professional technical team engaging in electric system and accessory product design and offering technical support including product research and development. Xuan Tong Electric is not only able to provide solutions for power distributing products, but also carry out application and development based on IEC61850 and IEC60870 system, etc.

ETCore core-board for electric industry designed and developed by Xuan Tong Electric widely applied as a core platform in electric industry and relevant area, such as direct current power distribution monitoring, distribution automation terminal, power relay protector, power quality monitoring and so on.

Xuan Tong Electric has established a solid cooperation with China Three Gorges Corporation (CTG), NARI Technology Development Co Ltd, Xuji Group Corporation and Schneider Electric.

After its domestic business achieves great success, Xuan Tong Electric starts its further business in overseas market. Xuan Tong Electric devotes itself to offer power products, design, research and development for clients all over the world. Employees of Xuan Tong Electric endeavor to create a better future for old and new clients.

 

Main Markets

Austria Austria

Canada Canada

U.S.A U.S.A

Factory Information

Guangzhou Xuan Tong Electric Technology Co. Ltd

Main Product

Related Products

Other buyers also search

Membership Grade

BUYER

Biz Pro VIP

SELLER

Biz Pro VIP
팝업닫기
Live Chat A new message arrives
from a business partner.

No Data

  • There is no data to load
  • Check out the My TK > My Inquiries list.
  • After agreeing to the use of the Live Chat service, the list is printed only when there is at least one history of receiving or sending a Live Chat request.

If you have not yet agreed to use the Live Chat service,

You can use the Live Chat freely after agreeing to the use of the Live Chat service.

View more
View more