PGS, GLBS, Gas Insulated Load Break Switches
Negotiable Min Order Quantity Unit
- Required Quantity
-
- Place of Origin
- South Korea
- Brand name
- VITZRO PGS & GLBS (GLBS & VPS TYPE)
- Payment Terms
- Negotiable
- Production method
- Negotiable
- Shipping / Lead Time
- Negotiable / Negotiable
- Keyword
- pgs, glbs, gas insulated load break switches for underground, gas insulated load break switches for pole mounted
- Category
- Power Supplies
VITZROTECH Co., Ltd.
- Verified Certificate
-
16
Product name | PGS, GLBS, Gas Insulated Load Break Switches | Certification | - |
---|---|---|---|
Category | Power Supplies | Ingredients | - |
Keyword | pgs , glbs , gas insulated load break switches for underground , gas insulated load break switches for pole mounted | Unit Size | - |
Brand name | VITZRO PGS & GLBS (GLBS & VPS TYPE) | Unit Weigh | - |
origin | South Korea | Stock | - |
Supply type | - | HS code | 853530 |
Product Information
1. VITZROTECH PGS & GLBS INTRODUCE (OUTDOOR TYPE)
(Gas Insulated Load Break Switches For Underground & Pole Mounted)
1-1 GLBS (Gas Insulated Load Break Switches For Underground)
● VITZRO TECH Gas Insulated Load Break Switch is a SF6 gas-insulated multi-circuit
switch that is installed on ground or underground at 22.9kV-Y or 22kVΔ underground
distribution line. It is an optimal product that uses SF6 gas as the insulating medium
superior for its arc extinguishing capability and the operating mechanism is a single-
operation method with 3-ground circuit for distinguishing the lines and branch lines.
● Switch Body
- It is a 3-phase integrated operating, single-tank type that consists of switch, auxiliaries based on the
operation method, cabinet based on the installation type and so on.
- It is equipped with a ground switch for each circuit and it is designed so that the operating state of the
ground switch can be easily checked outside.
- The body cabinet is 3 mm or bigger and the front part where the bushing is mounted is 5 mm or bigger
and both are manufactured using a stainless steel plate [STS304L] that can endure the inner gas
pressure. It is designed to have a stable structure with strong electrical and mechanical characteristics
and durability.
- Bolts are not used in order to prevent gas leak and it is completely enclosed by TIG welding. The
insulating material used in the inner part is the bisphenol, epoxy resin with excellent resistance to
electrical and mechanical characteristics and SF6 gas.
● Operating Device
- The operating device of the switch is divided into a main circuit part and earth part.
It is designed to require no special skills and all 3-phase contacts are opened / closed imultaneously
and the switching speed is always consistent regardless of the operation method.
- An automatic switch enables the mechanical closing/opening, electrical closing / opening and remote
operation (after installing a separate terminal and communication device) of the main circuit part.
However, the closing (earth)/opening of ground switch part can be manually operated on site.
- An interlock device is applied so that the closing (earth) operation of the ground switch is not done
unless the main circuit is opened and the closing operation of the main circuit is impossible at closing
(earth) state f the ground switch.
● Cabinet
- The cabinet and the base are made up of stainless steel plate [STS304L] with size of 2.0 mm or bigger
and 3.0 mm or bigger respectively. It is structured so that water does not form a pool in the cabinet.
- The cabinet is designed and manufactured so that it is easy to connect and disconnect cables, detect
current, check earth and phase and so forth by opening the cabinet door easily. In addition, automatic
voltage transformer (PT) for power control is installed in the lower part of the body and a door is
installed in the lower-side part of the cabinet for easy replacements.
- The cabinet is coated in Munsell NO. 7.5GY 3.5/2 (green color) when installed in green belt and in
Munsell NO. 5Y 7/1 (gray color) when installed in sidewalk and other areas.
- Product Standards : IEC 60265-1, IEC 60694
● Bushing Part
- It is structured to connect to the 600A deadbreak-type connector that is regulated in IEEE 386 and it is
installed in the body part using bolts and it is in an O-ring enclosed structure for full enclosure.
- A flange is made up of epoxy material and the flange surface that is connected to the body is
connected based on IEEE 386.
1-2 PGS (Gas Insulated Load Break Switches For Pole Mounted)
● VITZRO TECH Gas Insulated Load Break Switch is a switch that is used at 22.9kV-Y /
10kV-Δ overhead distribution line applied with SF6 gas as the insulating medium which
is superior in terms of arc extinguishing. It is an optimal product to distinguish the
overhead distribution line and to be used as a branch switch with the operating
mechanism, a spring toggle method.
● Switch Body
- It is a 3-phase integrated operating single-tank type that consists of a switch body, mounting tool and
control box. It easy to arm the concrete pole or power line and it can be installed stably. It is designed
in a simple structure for an easy maintenance work.
- A stainless steel plate ( STS304L) of 3 mm or bigger is used for the tank cabinet and it has a sufficient
electrical and mechanical strength. Each part of the switch is simple and durable and the opening and
closing are operated smoothly and accurately. There is no half-closing or half-opening during the
opening /closing operations, it is not opened / closed due to vibrations or other causes and it is
structured so that there is no water pool at any part of the switch.
- Bolts are not used in order to prevent gas leak and it is completely enclosed by TIG welding. The
insulating material used in the inner part is the bisphenol, epoxy resin with excellent resistance to
electrical and mechanical characteristics and SF6 gas.
- O-Ring that is used for the enclosure at the bonding part is made up of EPR and FPM that is heat-
proof, weather-protected and gas-proof and the surface of the O-Ring is covered with grease that is
heat- proof, weather-protected and gas-proof.
● Operating Device
- The operating device of the switch is divided into a main circuit part and earth part.
It is designed to require no special skills and all 3-phase contacts are opened/closed simultaneously
and the switching. speed is always consistent regardless of the operation method.
- In case of an automatic switch, it can be operated by an electrical switching device of the control box
and by a manual operating device of the body. It can be operated based on the designated operation
method [Local/Remote].
● Bushing Part
- It exceeds the standard impulse insulation density of the switch and all bonding parts are treated so
that gas does not leak and air does not get in. It is structured to maintain the mechanical sticking force.
- It is made up of a qualitative magnetic material that has the freezing and thermal capability, it is firm
enough to endure the mechanical impulse and it is moist-proof. In addition, it used a polysil insulating
material that is molded by an advance insulating material, polymer concrete, which our company
retains the patent, and it maintains the dielectric strength even at poor operational conditions since the
electrical and mechanical strength and arc extinguishing are superior.
● Outside Connecting Terminal
- It maintains the sticking force by connecting the terminal or lead-out line to the bushing.
- An insulation wire for high-voltage which is flexible and weather-protected is used and the nominal
sectional area of the conductor and the wire composition are 125 sq (159/1.0) or bigger for 400A and
200 sq (19/14/1.0) or bigger for 630A and the required length is 2 m.
- The lead-out line is water-proof which prevents the water from entering and the connecting part within
the mold cone is structured not to allow water from entering.
- The connecting part of mold cone and lead-out line is centralized with an electric field and it is glued
firmly so that the connecting part is not disconnected and its surface is smoothly treated.
Applied Standard IEC 60265-1
2. SPECIFICATIONS
2-1 GLBS (Gas Insulated Load Break Switches For Underground) SPECIFICATIONS
2-2 PGS (Gas Insulated Load Break Switches For Pole Mounted) SPECIFICATIONS
3. REMARKS
As one of the leader in electro-technical industry in Korea, We have been providing the best possible products, services, and solutions to the most of the industry such as nuclear and thermal power plant and substation facilities, and so on since its incorporation in 1955.
For the past 60 years, VITZROTECH was able to grow stably based on its firm foundation of modernized product facilities, improved Technical and quality standards, technical superiority balanced teamwork and professional service.
Leading the pleasant and auent field of electric power equipment with state-of-the-art technol-ogy, VITZROTECH is creating new value as well as present new standards, while making a dier-ence for a better future, based on thorough knowledge and skills in the fields of heavy electric equipment, power electronics and aerospace.
It is our sincere hope that the statement and information presented herein may help you the better understanding of VITZROTECH, as a financially responsible enterprise whose past performance and technical experience clearly expresses the sole commitment to your Project implementation.
We assure you of our preparation and cooperation to the fullest extent and hope to have the honor and opportunity to serve as the Reliable partner.
4. Contact
Request more information about our products
Mr.KIM J.W. / Manager of Plant Power System Business Unit
B2B Trade
Price (FOB) | Negotiable | transportation | - |
---|---|---|---|
MOQ | Negotiable | Leadtime | Negotiable |
Payment Options | Negotiable | Shipping time | Negotiable |
- President
- Byung-Eon, Yoo
- Address
- 605-2, Seonggok-dong, Ansan Si Danwon-gu, GYEONGGI-DO, 425-833, KOREA
- Product Category
- Active Components,Passive Components,Power Supplies
- Year Established
- 1968
- No. of Total Employees
- 101-500
- Company introduction
-
Business Type : Manufacture
Established Year : 1968
Employee Number : 312 (R&D Employee : 50)
Annual Sales : USD 97 Million (2013) / Export Amount : USD 20 Million (2013)
Certifications: ISO 9001:2000/KS A 14001:2004, ISO14001:2004/KS A 14001:2004, CESI, KEMA, UL
CERTIFICATION
VITZROTECH has been one of the recognized leaders in the electro-technical industry in Korea since1968.We are renowned for our skill in manufacturing V.I VCB, ACB, MCCB, ATS, protection relay(IED) and GIS as well as SwitchGear by our own technologies.
All our employees are professionally specialized in each part of research, design, simulation, testing, assembly, operation, service and quality control, and provide the appropriate consulting when necessary based on the extensive technical experience. We strongly believe in that success can only be achieved through the technical advancement and in doing so, we can never stop investing for the future through extensive research and development.
We know we can survive through our customers' success, and therefore, we are trying to provide the best possible customer support and service.
- Main Markets
-
Myanmar
Russia
Taiwan
U.S.A
- Factory Information
-
VITZROTECH Co., Ltd.
- Main Product